The PS-DL10 high-current generator (current booster) uses numerical control technology and has strong anti-interference capability. Its iron-core converter provides high output power with a compact, lightweight design. Used for thermal relays, motor protectors, contactors, circuit breakers, air switches, switchgear, breaker calibration, protection screen calibration, primary busbar protection, and current transformer transformation ratio testing, it is widely applied in scientific research, prod
The PS-DL10 high-current generator (current booster) uses numerical control technology and has strong anti-interference capability. Its iron-core converter provides high output power with a compact, lightweight design. Used for thermal relays, motor protectors, contactors, circuit breakers, air switches, switchgear, breaker calibration, protection screen calibration, primary busbar protection, and current transformer transformation ratio testing, it is widely applied in scientific research, prod
● Six-and-a-half-digit LCD display for voltage and current, offering higher display accuracy and more reliable experimental results
● 128×64 dot-matrix LCD display for clearer data presentation and faster reading
● Instrument display lock function for more accurate and faster readings, especially in transformer ratio tests
● 485 communication function to upload experimental results directly or store them on a USB flash drive (no manual logging required)
● Polarity measurement with automatic determination of transformer polarity, eliminating the need for separate polarity tests
● Chronograph with 0.1 ms–999999.9 ms LCD display range
● Elegant PVC front panel for improved resistance to dirt and wear
● High measurement accuracy: 0.5 class
● High power, compact design, and strong load capability
● Compact and lightweight: the volume is 30%–70% of comparable products, making it easy to transport
NAME |
PS-DL10 High-Current Generator |
Environmental group |
Classified as Group III instruments under GB6587.1-86 “General Specifications for Environmental Testing of Electronic Measuring Instruments” |
Input |
AC 50 Hz, 380 V |
Output |
Single-phase 0–2500.00 A AC current; current can be adjusted smoothly and continuously, with accuracy better than 0.1 |
|
The output current is a standard sine wave with low waveform “burr,” meeting power-system requirements. Ripple coefficient is less than 0.3%. |
|
Output current mode |
True RMS, continuously adjustable |
Output waveform |
Standard sine wave |
Output open-circuit voltage |
5 V |
Current accuracy |
Each current value can be adjusted smoothly and continuously, with accuracy better than 0.5. The current and voltmeter display are true RMS values, ensuring high accuracy and stability. |
Current stability |
0.1% |
Current waveform distortion |
THD 1% |
Protection |
Overcurrent, overvoltage |
|
The action time of the test element can be measured, and the locking action time can be recorded synchronously. Normally open and normally closed contacts are automatically identified. |
|
Timing range |
0.0001 s–9999.9999 s |
Resolution |
0.0001 s |
Power |
10000 VA |