PS-CB101 High-Voltage Switch Mechanical Characteristic Tester Circuit Breaker Tester

This HA stand switch is suitable for all types of SF6 switches, GIS combined appliances, vacuum switches, and oil switches produced at home and abroad. The high-voltage switch mechanical characteristic tester measures mechanical dynamic characteristic parameters of high-voltage circuit breakers of different voltage levels, including low oil, high oil, vacuum, and sulfur hexafluoride types. As high-voltage circuit breakers perform both control and protection functions in power systems, mechanical


This HA stand switch is suitable for all types of SF6 switches, GIS combined appliances, vacuum switches, and oil switches produced at home and abroad. The high-voltage switch mechanical characteristic tester measures mechanical dynamic characteristic parameters of high-voltage circuit breakers of different voltage levels, including low oil, high oil, vacuum, and sulfur hexafluoride types. As high-voltage circuit breakers perform both control and protection functions in power systems, mechanical

Product Selling Points

 

  1. 1. This device is an embedded industrial computer. The main board is based on Cortex™-A8, with a main frequency of 1 GHz, 1 GB flash memory, and a boot time of 16 seconds. It features a large 8.4-inch color screen and runs on a Windows operating system. The operation interface is intuitive and user-friendly, with a touch screen. It supports Chinese and English input, making it easy for on-site operators to use.
  2. 2. High-speed thermal printer for convenient on-site printing of test data.
  3. 3. An integrated operating power supply eliminates the need for a secondary on-site power supply. It provides a DC 5∼270 V adjustable output with a current of 20 A. The operating voltage for the closing and opening coil can be set arbitrarily, enabling low-voltage operation tests of the circuit breaker.
  4. 4. Equipped with a linear sensor, rotation sensor, universal sensor, and brackets, as well as a special fixed multi-functional joint for fast and simple installation.
  5. 5. Suitable for SF6 switchgear of all types, GIS combined electrical equipment, vacuum switches, and oil switches produced domestically and abroad.
  6. 6. One switch operation collects all data and graphics.
  7. 7. The host can store 30,000 groups of current test data (expandable via memory card). The real-time clock supports convenient archiving.
  8. 8. USB flash drive (U disk) interface for directly saving data to a U disk and transferring it to a computer for analysis and record keeping.
  9. 9. Measures 12 metal contact fracture channels simultaneously: 6 main fractures and 6 auxiliary fractures.
  10. 10. Includes an envelope curve. The standard envelope curve is generated based on values tested by the switch for analysis and comparison, as well as switch vibration frequency analysis.
  11. 11. Built-in anti-interference circuitry ensures reliable use in 500 kV substations.
  12.  
Product Parameters

 

Time measurement

12-channel inherent opening/closing time

Different time periods in the opening/closing phase

Differences in opening/closing phases across different time periods

Closing/opening bounce time (bounce times)

Internal trigger test range

0.01 ms∼20 s

Resolution

0.01 ms

Open contact test range

0.01 ms∼200 s

Resolution

0.1 ms

Accuracy within 1000 ms

0.05% ± 1 word

Speed measurement

Opening speed (opening only) / closing speed (closing only)

Average speed over a specified time period (stroke period or angle period)

Speed range

1 mm sensor: 0.01∼25.00 m/s

0.1 mm sensor: 0.001∼2.50 m/s

360° angle sensor: 1 cycle / 0.25°

Stroke measurement

Moving contact stroke (stroke)

Contact stroke (opening distance)

Overtravel

Overshoot stroke or rebound stroke

Measuring range

Linear sensor

50 mm

Measuring range

0∼50 mm

Resolution

0.1 mm

360 line sensor

360°

Measuring range

0∼1000 mm

Resolution

0.25

Acceleration sensor measuring range

0∼300 mm

Resolution

0.1 mm

Current display

Maximum current: 30 A

Resolution

0.01 A

Instrument power

AC 220 V ± 10%; 50 Hz ± 5%

DC power output

DC 5∼270 V continuously adjustable; DC110 V ≤ 30 A (short time); DC220 V ≤ 20 A (short time)

Open contact trigger voltage

AC/DC 10–300 V; current ≤ 120 A

Isolation switch measuring range

Voltage output

DC 5∼270 V (adjustable)

Power output time

0.01∼20 seconds (settable)

The maximum acquisition time of fracture signals is 200 seconds.

It can measure closing/opening time of the fractures, the three-phase different periods, bounce time, and the number of times.

Host dimensions

360 × 260 × 170 mm

Operating environment

–20 °C∼+50 °C

Relative humidity

≤ 90%