PS-CTPT1000 Frequency Conversion Transformer Tester Ct Pt Tester

Built with a high-performance DSP and ARM and advanced manufacturing technology, this professional testing instrument for transformers delivers stable, reliable performance with complete functions, high automation, and efficient testing. It is designed for use in the power industry.


Built with a high-performance DSP and ARM and advanced manufacturing technology, this professional testing instrument for transformers delivers stable, reliable performance with complete functions, high automation, and efficient testing. It is designed for use in the power industry.

Product Selling Point Introduction

 

  1. Comprehensive functionality: it not only meets the excitation characteristics (i.e., volt-ampere characteristics), transformation ratio, polarity, secondary winding resistance, secondary load, ratio difference, and phase angle difference requirements of various CTs (such as protection, measurement, and TP), but also enables testing of the excitation characteristics, transformation ratio, polarity, secondary winding resistance, ratio difference, and phase angle difference of various PT electromagnetic units.
  2. Inflection point voltage/current, 10% (5%) error curve, accuracy limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), remanence factor (Kr), saturation characteristics, and parameters such as unsaturated inductance.
  3. The test complies with various transformer standards, including GB1208 (IEC60044-1), GB16847 (IEC60044-6), GB1207, etc. The relevant standard is automatically selected for testing based on the transformer type and rating level.
  4. Using the advanced low-frequency test principle, it can handle CT testing with an inflection point voltage of up to 45 kV.
  5. Friendly and user-friendly interface with a fully Chinese graphical interface.
  6. The device can store up to 2,000 sets of test data without loss after power failure. After the test is completed, data can be saved to a PC via a USB flash drive; the software can then analyze the data and generate a Word report.
  7. Simple and convenient operation. For CTs, one-key operation supports direct resistance, excitation, transformation ratio, and polarity tests. Except for the load test, all other CT tests use the same wiring method.
  8. Easy to carry: device weight is <9 kg.

 

Product Parameter

 

Test purpose

Protection class CT, protection class PT

Output

0~180 Vrms, 12 Arms, 18 A (Peak)

CT ratio
Measurement

Scope

1~40000

 

Precision

±0.05%

PT ratio
Measurement

Scope

1~40000

 

Precision

±0.05%

Phase measurement

Precision

±5 min

 

Resolution

0.5 min

Secondary winding resistance measurement

Scope

0~300 Ω

 

Precision

2% ±2 mΩ

AC load measurement

Scope

0~1000 VA

 

Precision

2% ±0.2 VA

Input power supply voltage

AC 220 V ±10%, 50 Hz

Working environment

Temperature: -10°C~50°C, Humidity: ≤90%

Size and weight

Size: 340 mm x 300 mm x 150 mm; Weight: <9 kg

 

Video