PUSH Electrical PS-DCA10 DC resistance tester

The instrument features a new power supply technology with a compact, lightweight design, delivering high output current with good repeatability and strong anti-interference performance. It also includes a complete protection function.


The instrument features a new power supply technology with a compact, lightweight design, delivering high output current with good repeatability and strong anti-interference performance. It also includes a complete protection function.

Product Selling Point Introduction

 

  1. The entire unit is controlled by a high-speed single-chip microcomputer, offering a high degree of automation, as well as simple operation.
    2. The new power-supply technology provides multiple current ranges and a wide measurement range. The test current can be automatically selected according to the load.
    3. 480 × 270 true-color LCD touch screen for clear display under strong lighting, with a dual-purpose touch screen / key interface.
    4. RS232 and USB interfaces enable communication with a computer (optional) and support U disk storage.
    5. Comprehensive protection functions reliably protect the instrument from the impact of back EMF, ensuring more dependable performance.
    6. An audible discharge alarm with on-screen prompts makes discharge status clear and reduces the risk of misoperation.
    7. Fast response and stable measurement data, with automatic data refreshing during the test process.
    8. Intelligent power-management technology effectively reduces internal instrument heating and saves energy.
    9. Non-power-down clock and non-power-down memory permanently save data.

 

Product Parameters

 

Output current

Automatic, 10A, 5A, 1A, 200mA, 40mA, <5mA

Resolution

0.1 μΩ

Range (including leads)

100 Ω ~ 100 kΩ   (≤ 5 mA range)

 

0.3 Ω ~ 500 Ω   (40 mA range)

 

0.1 Ω ~ 100 Ω   (200 mA range)

 

0.06 Ω ~ 20 Ω   (1 A range)

 

0.03 Ω ~ 3.2 Ω   (5 A range)

 

0 ~ 1.6 Ω   (10 A range)

 

0 ~ 100 kΩ   (Automatic)

Accuracy

0.2% ± 2 digits (reference: numeric value)

Operating temperature

-10 ~ 40 ℃

Operating humidity

<80% RH, non-condensing