The instrument provides standard four-phase voltage and three-phase current output (six-phase voltage and six-phase current output). It is suitable for testing traditional relays and protection devices, as well as modern microcomputer protection, particularly transformer differential power protection and standby automatic transfer switching devices. Model No.: PS-902/903, PS-1200, PS-802/1620/1630.
The instrument provides standard four-phase voltage and three-phase current output (six-phase voltage and six-phase current output). It is suitable for testing traditional relays and protection devices, as well as modern microcomputer protection, particularly transformer differential power protection and standby automatic transfer switching devices. Model No.: PS-902/903, PS-1200, PS-802/1620/1630.
Core Description
The instrument provides a four-phase voltage output and three-phase current output (six-phase voltage output and six-phase current output). It can be used to test a wide range of conventional relays and protection devices, as well as modern microcomputer-based protection systems—particularly transformer differential protection and standby automatic transfer switching devices. The testing process is more convenient and provides improved performance.
|
3 × 20A |
|||
|
Single-phase current output (effective value) |
0 — 20A / phase |
Accuracy |
0.2% ± 5mA |
|
Three-phase parallel output (effective value) |
0 — 60A / three-phase in-phase parallel output |
||
|
Allowable long-term phase current (effective value) |
10A |
||
|
Maximum output power per phase |
200VA |
||
|
Maximum output power for three-phase parallel current |
600VA |
||
|
Maximum allowable working time for three-phase parallel current output |
30s |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.01Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
|
3 × 30A |
|||
|
Single-phase current output (effective value) |
0 — 30A / phase |
Accuracy |
0.2% ± 5mA |
|
Three-phase parallel output (effective value) |
0 — 90A / three-phase in-phase parallel output |
||
|
Allowable long-term phase current (effective value) |
10A |
||
|
Maximum output power per phase |
300VA |
||
|
Maximum output power for three-phase parallel current |
800VA |
||
|
Maximum allowable working time for three-phase parallel current output |
30s |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.01Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
|
3 × 30A |
|||
|
Single-phase current output (effective value) |
0 — 40A / phase |
Accuracy |
0.2% ± 5mA |
|
Three-phase parallel output (effective value) |
0 — 120A / three-phase in-phase parallel output |
||
|
Allowable long-term phase current (effective value) |
10A |
||
|
Maximum output power per phase |
420VA |
||
|
Maximum output power for three-phase parallel current |
1000VA |
||
|
Maximum allowable working time for three-phase parallel current output |
10s |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.01Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
|
6 × 20A |
|||
|
Single-phase current output (effective value) |
0 — 20A / phase |
Accuracy |
0.2% ± 5mA |
|
Three-phase parallel output (effective value) |
0 — 120A / six same-phase parallel output |
||
|
Allowable long-term phase current (effective value) |
10A |
||
|
Maximum output power per phase |
200VA |
||
|
Maximum output power for three-phase parallel current |
800VA |
||
|
Maximum allowable working time for three-phase parallel current output |
30s |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.01Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
|
6 × 30A |
|||
|
Single-phase current output (effective value) |
0 — 30A / phase |
Accuracy |
0.2% ± 5mA |
|
Three-phase parallel output (effective value) |
0 — 180A / six same-phase parallel output |
||
|
Allowable long-term phase current (effective value) |
10A |
||
|
Maximum output power per phase |
300VA |
||
|
Maximum output power for three-phase parallel current |
1000VA |
||
|
Maximum allowable working time for three-phase parallel current output |
30s |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.01Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
DC current source
|
DC current output: 0 — ± 10A / phase, accuracy |
0.2% ± 5mA |
AC Voltage Source
|
Single-phase voltage output |
(effective value) 0 — 125V / phase |
Accuracy |
0.2% ± 5mV |
|
Line voltage output (effective value) |
0 — 250V |
||
|
Phase voltage / line voltage output power |
75VA / 100VA |
||
|
Frequency range |
0 — 1000Hz |
Accuracy |
0.001Hz |
|
Harmonic frequency |
2 — 20 times |
||
|
Phase |
0 — 360° |
Accuracy |
0.1° |
DC voltage source
|
Single-phase voltage output amplitude |
0 — ± 150V |
Accuracy |
0.2% ± 5mV |
|
Line voltage output amplitude |
0 — ± 300V |
||
|
Phase voltage / line voltage output power |
90VA / 180VA |
||
Switching value terminal
|
Switching value input terminal |
8 pairs |
|
Dry contact |
1 — 20mA, 24V, internal active output of the device |
|
Polarity reversal |
Passive contact: low-resistance short-circuit signal |
|
Active contact |
0 — 250V DC |
|
Switching value output terminal |
4 pairs, dry contact, breaking capacity: 110V / 2A; 220V / 1A |
Other
|
Time range |
1ms — 9999s; measurement accuracy: 1ms |
|
Dimensions and weight |
410 × 190 × 420mm3, approximately 18kg |
|
Power supply |
AC 220V ± 10%, 50Hz, 10A |